How
to Wire the Series
980/985
The Series
980/985
wiring is illustrated by model number option. Check the
unit sticker on the control and compare your model number to those shown
here and also the model number breakdown in the back of this manual.
Series
980/985
internal circuits appear “inside“ the line drawing of the
980/985,
while connections and terminal designations appear “outside” the line drawing.
All outputs are referenced to a de-energized state. The final wiring figure is a
typical system example.
All wiring and fusing should conform to the National Electric Code and to any
locally applicable codes as well
.
When you apply power without sensor inputs on the terminal strip, the Series
980/985
will display
“-
-
”
-
in the Upper display, and a
"O"
in the Lower display.
Press the AUTO/MANUAL key twice, and an
ER
7 is displayed for one second.
This error indicates an open sensor. Remove power to the control and connect
the sensor properly, see Page 14.
II
II
Jumper
#4
to
#6
and
Jumper
#5
to
#7
for
115
VAC operation
0
II
0
Jumper
#5
to
#6
for
230 VAC operation
L2
Earth
Ground
Figure 8
-
115 VAC Power
Wiring
0
CAUTION:
To
avoid potential
electric
shock, use
National
Electric
Code (NEC) safety
practices when
wiring and connect-
ing this unit to a
power source and to
electrical sensors or
peripheral devices.
Figure 9
-
230 VAC Power
Wiring
Install
and
Wire
Chapter
2
WATLOW
Series
980/985
User’s
Manual
13
Comentários a estes Manuais